Improving Effective Energy-Efficient Commercial Package Dedicated Outside Air Systems Located in Hot-Humid Climate Zones

Secondary Author(s)

Salyer, David

Report Number

FSEC-PF-476-19

URL

http://publications.energyresearch.ucf.edu/wp-content/uploads/2019/04/FSEC-PF-476-19.pdf

Keywords

Air Conditioning; Hot Humid Climates; Dehumidification; HVAC; Ventilation; Cooling; Commercial; Energy-Efficient Commercial Package; Dedicated Outside Air Systems; Hot-Humid Climate Zones; Variable Speed Fan Motors; Variable Refrigerant Flow Technologies

Abstract

Mechanically distributing an appropriate amount of outside air (OA) ventilation throughout a commercial building with variable occupancy can be challenging without over-ventilating, and can have significant energy costs associated. This particularly tests engineers that seek to optimize energy-efficiency with effective variable OA throughout different zones.

Conditioning OA in hot-humid climates takes special consideration due to the very high latent loads that must be removed. Simple HVAC systems must constantly operate the supply fan to meet ventilation requirements, even if indoor comfort temperature has been met. This method of operation can result in high indoor humidity during periods of low cooling load. It may also result in over-cooling if the setpoint is lowered to increase dehumidification, particularly with conventional packaged and split HVAC systems.

Using a dedicated outside air system (DOAS) to handle 100% of the ventilation air has been part of the solution to improve moisture control and over-cooling issues. This improves comfort control by dedicating systems properly sized solely for heating and air conditioning (HAC) loads, and dedicating DOAS specifically sized for the OA ventilation load. It can also make it easier to distribute variable amounts of OA to different zones. While DOAS help improve control, there are still challenges to managing energy-efficient OA conditioning and distribution in buildings with variable cooling loads and occupancy. Many packaged DOAS use air distribution fans that operate at constant speed and vary airflow by simply using air damper controls. Fixed-flow designs have more limitations to energy savings potential than variable supply flow DOAS.

The advancement of variable speed fan motors and variable refrigerant flow technologies have made their way into space conditioning systems and offer good energy savings potential as they can operate very efficiently at varying load levels. These advancements had recently been developed and applied to a package DOAS, and a field study was completed through third-party evaluation. The variable-capacity DOAS was put into a field trial at a high school cafeteria. Testing showed that the unit was able to deliver 55°F-60°F (12.8°C-15.6°C) dewpoint supply air under a variety of weather conditions and at variable ventilation rates. Analysis indicated a potential 77% reduction in annual DOAS energy when a schedule-based controlled fixed-flow DOAS (EER=10) was replaced with the variable capacity DOAS unit using CO2 demand-based control. Demand control accounted for about 36% of the total savings.

Date Published

1-12-2019

Identifiers

41

Notes

Copyright 2019 ASHRAE. This paper was published in the ASHRAE Technology Portal.

Subjects

Energy consumption; Air conditioning; Ventilation; Humidity--Control; Energy conservation

Local Subjects

Buildings - Air Conditioning; Buildings - Commercial; Buildings - Cooling; Buildings - Dehumidification; Hot Humid Climates; Buildings - HVAC; Buildings - Ventilation

Type

Text; Document

Collection

FSEC Energy Research Center® Collection