Title
Energyplus And Champs-Multizone Co-Simulation For Energy And Indoor Air Quality Analysis
Keywords
CHAMPS-Multizone; Co-Simulation; Energy simulation; EnergyPlus; Indoor air quality simulation
Abstract
This paper presented a co-simulation method using EnergyPlus and CHAMPS-Multizone for combined energy efficiency and IAQ analysis. In each time step, the CHAMPS-Multizone simulates the pollutant balance, and the ventilation rate required to control the contaminant concentrations under pre-established threshold values. EnergyPlus uses the ventilation rate to simulate the heat, air, and moisture balance, and the energy and daylighting performance. The Building Controls Virtual Test Bed (BCVTB) is used for the run-time data exchange. A 3-zone building was used to test and verify the method. The co-simulation model was developed, implement in a Virtual Design Studio (VDS) software framework with graphical user interface for integrated building system design, and found to be especially useful in analyzing the interaction between IAQ and energy efficiency measures.
Publication Date
1-1-2014
Publication Title
Indoor Air 2014 - 13th International Conference on Indoor Air Quality and Climate
Number of Pages
69-76
Document Type
Article; Proceedings Paper
Personal Identifier
scopus
Copyright Status
Unknown
Socpus ID
84924649876 (Scopus)
Source API URL
https://api.elsevier.com/content/abstract/scopus_id/84924649876
STARS Citation
Chen, Yixing; Gu, Lixing; Zhang, Jianshun; and Kong, Meng, "Energyplus And Champs-Multizone Co-Simulation For Energy And Indoor Air Quality Analysis" (2014). Scopus Export 2010-2014. 9963.
https://stars.library.ucf.edu/scopus2010/9963