Title

Monitoring Of Distribution Water Qualities Under Various Source Water Blending

Keywords

Advanced surface water treatment; Pipe corrosion; Pipe distribution water qualities; Sea water desalination; Source water blending

Abstract

The main goal of this large-scale pilot distribution study was to systematically investigate the impacts of blending different source waters on distribution water qualities. The principal source waters investigated were conventionally treated ground water (G1), surface water processed by enhanced treatment (S1), and desalted seawater by reverse osmosis membranes (RO). Due to the nature of raw water quality and associated treatment processes, G1 water had high alkalinity, while S1 and RO sources were characterized as high sulfate and high chloride waters, respectively. One year of pilot pipe study demonstrated that water quality was significantly deteriorated by increased color when source water blends with characteristics different from historic groundwater were introduced to pipe distribution systems. Elevated color was associated with release of iron corrosion products, mainly from aged unlined cast iron pipes. Iron release increased significantly when exposed to RO and S1 waters: that is, the greater iron release was experienced with alkalinity reduced below the background of G1 water. Lead and copper release to water, on the other hand, enhanced with the application of RO and G1 waters, respectively. © Springer Science + Business Media, Inc.

Publication Date

8-25-2006

Publication Title

Environmental Monitoring and Assessment

Volume

117

Issue

1-3

Number of Pages

59-71

Document Type

Article

Personal Identifier

scopus

DOI Link

https://doi.org/10.1007/s10661-006-7672-8

Socpus ID

33747450955 (Scopus)

Source API URL

https://api.elsevier.com/content/abstract/scopus_id/33747450955

This document is currently not available here.